Pneumercator TMS3000

Pneumercator TMS3000

Item #TMS3000

The Pneumercator TMS3000 Tank Management System with EPA-compliant in-tank lead detection is a truly low cost, high performance solution designed to meet all of your environmental compliance and inventory management needs. Complete with every feature you need, the TMS3000 has a simple, user friendly interface. Extremely flexible, modular system architecture. Completely field configurable and upgradeable.

Pneumercator TMS3000 Benefits

  • Provisions for monitoring up to 40 intrinsically safe discrete sensor inputs, including discriminating and non-discriminating interstitial, overfill, and secondary leak containment sensors. 
  • Sensor wiring fault detection feature ensures correct installation when used with Pneumercator "F" series fault output discrete sensors.
  • Plug-in Relay-I/O cards provide up to 8 fully programmable NO/NC relay contact outputs with 8 non-intrinsically safe dry contact inputs, or up to 32 fully programmable NO relay contact outputs.
  • Plug-in Analog Output card provides up to 12 fully programmable analog outputs.
  • Third party certified for 0.1 or 0.2 gph in-tank leak detection in tanks up to 75,000 gallons.
  • Remotely monitor and program via an included RS-232 serial port, from a central location via optional, secured, internal modem, or from a LAN/WAN via optional, secured, internal network interface card. RS-485 port included for connection to Pneumercator "smart" peripherals, such as remote display and annunciator panels.
  • Automatic shift inventory, unsupervised deliveries, bulk sales, alarms, leak test, water removal, product ordering, and theft logging.
  • NEMA 4 or 4X enclosure options available for harsh outdoor environments
  • Easy to install and use; system set-up can be performed using the front panel pushbuttons, or, via the RS-232, modem port, or TCP/IP.

Console:

  • Dimensions (W x H x D): 11.8” x 11.5” x 7.7” (300mm x 292mm x 178mm)
  • Weight: 19 lb (8.6 kg) (4-Tank w/ Printer), 21.5 lb (9.8 kg) (12-Tank w/ Printer)
  • Operating Temperature: -40 ºF to 160 ºF (-40 ºC to 70 ºC) w/o Printer; -5 ºF to 140 ºF (-20 ºC to 60 ºC) w/ Printer
  • Humidity: 95% Non-condensing
  • Enclosure Rating: Locking NEMA 12 (IP52), NEMA 4 (IP56) or NEMA 4X (IP56) (304 SS)
  • Power Requirements: 115/230 VAC ±15% (w/o Printer) Switchable, 50-60 Hz, 20 W Max.
  • Memory: Configuration/Setup Data – EEPROM, 50 year data retention, no batteries
  • Log Reports and Real-Time Clock – Lithium Battery-Backed RAM, 5-10 year data retention
  • Audible Alarm: 85 db
  • Display: 9-Character, Super-Bright Sunlight-Readable LED Data Display, Readable from 25’ (7.6 m)
  • Ultra-High Intensity Alarm LEDS, Visible from 75’ (22.9 m)
  • Communications: RS-232 Included Standard, RJ-13 Jack (Additional RS-232 port accessible when configured without printer or modem)
  • RS-485 Included Standard, RJ-13 Jack (For Pneumercator Peripherals)
  • Internal, Secured Modem, Fax / Modem
  • Probe / Sensor Capacities: 4/40, 8/32 or 12/24 (Probes/Sensors)
  • All Sensor Inputs Supervised-Wiring-Ready

I/O, Non-Haz.: Expansion Options (2 slots available):

  • 4 Relays, 1 Form C, Rated 10 A@120, 6 A@240 VAC, w/ 4 Opto-Isolated Inputs
  • 8 Relays, 1 Form A, Rated 5 A@120, 5 A@240 VAC, w/ 8 Opto-Isolated Inputs
  • 16 Relays, 1 Form A, Rated 5 A@120, 5 A@240 VAC
  • 6 or 12-Ch. Programmable Analog Outputs:
  • 0-1 mA, 0-20 mA, 0-24 mA, 4-20 mA, 0-5 VDC, 1-5 VDC

Probe:

  • Technology: Magnetostrictive, Dual Float, w/ reflection resolution doubling
  • Materials: Shaft: 316 SS or PVDF; Floats: 316 SS, Buna-N, Urethane, or PVDF 
  • Mounting: In-Tank Leak Testing: 4” (102mm) diameter riser; Inventory Only: 2” (51 mm) minimum riser or direct bushing / flange mount 
  • Temperature Sensing: 5 Thermistors in shaft, 1 in probe head 
  • Location Approval: UL Class I, Div 1, Groups C and D; cUL Class I, Zone 0, Group IIB 
  • Operating Temperature: -40 ºF to 175 ºF (-40 ºC to 80 ºC) 
  • Operating Pressure: 150 PSIG (1034 kPa) 316 SS, 50 PSIG (345 kPa) PVDF 
  • Field Wiring: 22AWG, 2-Conductor twisted pair w/ shield; Belden 8441, 8761, Alpha 1736C or equiv., max. length 3000’ to 4600’ (914 m to 1402 m) 

Accuracy (Minimum) MP45xS: 

  • Product Level: 0.0005” (0.013 mm) 
  • Water Level: 0.001” (0.025 mm)
  • Temperature: 0.001 ºF (0.0006 ºC)

Accuracy (Minimum) MP46x: 

  • Product Level: 0.01” (0.25 mm) 
  • Water Level: 0.01” (0.25 mm)
  • Temperature: 0.001 ºF (0.0006 ºC)  

Sensors:

  • ES825-200F Electronic, Discriminating - Containment, Manway and Piping Sumps, Dispenser Pan, Dry Annular, Includes Fault Detection Feature as Standard
  • ES825-100F Electronic, Non-Discriminating - Containment, Manway and Piping Sumps, Dispenser Pan, Dry Annular, Includes Fault Detection Feature as Standard
  • LS600LD Float, Containment, Manway and Piping Sumps, Dispenser Pan
  • LS600xx Multi-Float, High / Low Level and Pump Control
  • RSU800 Float, Wet Annular / Reservoir
  • LS610 Float, Dry Annular
  • HS100D Polymer / Float – Wet Well, 10’ to 25’ (3 m to 7.6 m) depth
  • HS100ND Polymer – Dry Containment, 1’ to 45’ (0.3 m to 13.7 m) length

Most sensors are available with Fault-Detect Supervised sensor and wiring option. Add “F” Suffix to Model Number

Console:

  • Internal impact printer for automatic or on-demand reports
  • Outdoor printer available
  • Optional Power Requirements: 8-16 VDC or 16-60 VDC power requirements
  • Optional Communications: Network Interface or ModBus

Remote Displays:

  • ETD1000 Addressable (up to 16), Multi-Drop, Remote Electronic Tank Display Panel
  • TD1000 Tandem Remote Display

Approvals/Certifications:

  • UL/cUL approved, File #E139464
  • FCC Part 15B, Part 68

Third-Party Approved, EPA-Compliant: 

  • Up to 20,000 Gal. (75,708 liter) tank capacity, minimum tank inventory for test 20% 
  • 0.2 GPH (0.8 LPH) Leak Test: Pd = 99.9%, Pfa = 0.1% 
  • 0.2 GPH (0.8 LPH) Quick Test: Pd = 95%, Pfa = 5% 
  • 0.1 GPH (0.4 LPH) Precision Test: Pd = 95.3%, Pfa = 4.7% 
  • Up to 75,000 Gal. (283,906 liter) tank capacity, minimum tank inventory for test 50% 
  • 0.2 GPH (0.8 LPH) Leak Test: Pd = 97.3%, Pfa = 2.7%