3M Scotchcast Connector Sealing Pack

3M Scotchcast Connector Sealing Pack

Item #3570

Scotchcast™ connector sealing pack. Insulates and provides protection for electrical spring connectors against dust, soil, water, and other environmental elements. Each sealing pack contains a specific amount of the two-part 3M™ Scotchcast™ Epoxy Resin 3570G-N in a unique closed mixing pouch. The resin generates its own heat to cure and its compatibility with spring connectors makes this sealing pack a convenient insulating and encapsulating resin for electrical spring connections. (Veeder Root P/N 514100-304.)

Price

$7.95

  • Thermosetting; will not melt or run once it cures
  • Generates its own heat to cure
  • Stable in applications at elevated temperatures up to 121°C
  • Unique closed mixing pouch for mixing the resin and encapsulating the appropriate spring connectors
  • Tough, excellent multi-purpose moisture sealing resin
  • Density: (ASTM D792) 0.65 oz/cu in (1,13 g/cc)
  • Hardness: (ASTM D2240) 60 Shore D
  • Tensile Strength: (ASTM D638) 1779 psi (125 kg/cm2)
  • Elongation: (ASTM D638) 57%
  • Glass Transition Temperature, Tg (DSC): 70ºF (21ºC)
  • Maximum Exotherm (100g) (ASTM D2471-99): 140°F (60°C)
  • Gel Time @ 73°F (23°C) (ASTM D2471-99): 8-12 minutes
  • Weight Loss, Heat Aging (3M Method TM-451) @ 250°F (121°C): 1 week 3.31%, 2 weeks 5.33% 
  • Adhesion to Metals (lb/in2) (3M TM456): Copper - 112.5, Brass - 109.25, Steel - 172.35, Aluminum - 64.8
  • Adhesion to Cable Jackets  (lb/in2) (3M TM457): Vinyl - 53.8, Neoprene - 112.5, Nylon - >26.5, XLPE - 223.4
  • Weight Gain (1 week, boiling water) (ASTM D471): 4.76%
  • Dielectric Strength (ASTM D149): 435 V/mil (17.1 kV/mm) 
  • Dielectric Constant @ 60Hz (ASTM D150): 73°F (23°C) at 2.2 pF, 194°F (90°C) at 8.9 pF 
  • Dissipation Factor @ 60Hz (ASTM D150): 73°F (23°C) at 8.8%, 194°F (90°C) at 187%

 The 3M™ Scotchcast™ Connector Sealing Pack 3570G-N should remain sealed in the guard bag (white aluminized bag) until ready to use. In cold weather, warm closed mixing pouch to 50°F (10°C) or warmer prior to mixing. Keep in a warm area, such as truck cab or inside pocket, until ready to use. For best results, use within 1 hour of opening the guard bag.